1756-OF4 Übersicht

The Allen-Bradley 1756-OF4 is a four-channel, non-isolated analog output module for the ControlLogix platform, providing ±10 VDC voltage outputs or 0–20 mA current outputs through a 20-pin removable terminal block in an open-style module.

An analog output module is an industrial programmable-controller I/O device that converts controller data into continuously variable voltage or current signals. It sits between the ControlLogix controller and field equipment in the hierarchy of industrial automation: PLC system, programmable automation controller, I/O module, and analog output interface.

The module provides four selectable outputs, 15-bit resolution, scaling, calibration, ramping, clamping, configurable program and fault states, and open-circuit detection for current outputs. Verified distributor data identifies 0–20 mA current operation, ±10 VDC voltage operation, and a 20-pin open-style format. A service-manual source additionally specifies 650 nA per bit across 21 mA for current output and 320 µV per bit across 10.5 V for voltage output.

The ControlLogix backplane connection and removable terminal block support modular cabinet installation. Published operating temperature data spans 0°C to 60°C, while the module draws 150 mA at 5.1 VDC or 120 mA at 24 VDC from the backplane. Series B and C hardware has higher power requirements than Series A, an important replacement-planning consideration.

Typical uses include proportional control valves, variable-speed drives, positioning equipment, current-loop transmitters, and test systems. Voltage outputs suit drives and positioners accepting bipolar analog commands; current outputs support two-wire process transmitters and provide open-circuit fault detection.

Before installation, verify the ControlLogix chassis, controller compatibility, module series, terminal-block wiring, output mode, grounding, and field-device loop resistance. Keep voltage and current wiring distinct and configure output behavior for safe process states during controller faults or disconnects.

This page consolidates verified manufacturer and distributor specifications, sourcing links, technical comparisons, and engineering guidance. Because no verified drop-in replacement was found, it does not present unverified substitutes or cross-brand modules as pin-compatible alternatives.

Drop-in-Alternativen für 1756-OF4 – gleiches Gehäuse, Pin-kompatibel. Bauteile mit anderem Gehäuse, die eine PCB-Überarbeitung erfordern, sind ausgeschlossen.

Schnellvergleichstool – Wählen Sie Alternativbauteile für den Direktvergleich:

Für dieses Produkt sind keine Drop-in-Alternativen verfügbar.

Alternativen anfordern

1756-OF4 Spezifikationen (herstellerveröffentlicht)

Product Type ControlLogix analog output module
Number of Analog Output Channels 4 channels
Voltage Output Range ±10 VDC
Current Output Range 0–20 mA
Output Resolution 15 bit
Current Output Resolution 650 nA/bit across 21 mA
Voltage Output Resolution 320 µV/bit across 10.5 V
Isolation Non-isolated outputs
Ausgangstyp Single-ended voltage/current
Terminal Connector 20-pin removable terminal block
Enclosure Style Open style
Betriebstemperatur 0°C to 60°C
Backplane Current at 5.1 VDC 150 mA
Backplane Current at 24 VDC 120 mA
Current Output Fault Detection Open-circuit detection
Output Configuration Features Scaling, calibration, ramping, clamping, and configurable program/fault states
Platform Allen-Bradley ControlLogix
Product Weight 0.75 lb
Warranty 2 years

1756-OF4 Schnittstellen & Anschlüsse

Für 1756-OF4 ist keine vom Hersteller veröffentlichte Schnittstellenliste verfügbar. Details zu Anschlüssen und Headern finden Sie in der Herstellerdokumentation.

Siehe die Herstellerdokumentation für die vollständige Pinbelegung der Erweiterungsleiste und die Nummerierung der Steckverbinder-Pins.

Leistungs- und thermische Eigenschaften

Betriebstemperatur 0°C to 60°C

Vom Hersteller veröffentlichte Leistungs- und thermische Parameter für 1756-OF4.

Typische Anwendungen

1756-OF4 ist geeignet für 6 Anwendungs: Proportional Control Valve Positioning, Variable-Speed Drive Speed Reference, Current-Loop Process Transmitter Control, Positioning Axis Command Interface, Industrial Test and Calibration Systems, Machine Tool and Packaging Line Control.

⚡

Proportional Control Valve Positioning

The Allen-Bradley 1756-OF4 fits process systems that command proportional valves from a ControlLogix controller. Its four channels can provide ±10 VDC to compatible bipolar valve amplifiers or 0–20 mA to current-input actuators, while scaling and ramping help convert controller values into controlled valve movement. Non-isolated outputs require careful common-reference wiring. Before energizing an actuator, configure program and fault states, verify the field-device limits, and confirm polarity to avoid unexpected full-scale travel.

🏭

Variable-Speed Drive Speed Reference

The 1756-OF4 is appropriate when a ControlLogix system must send a continuous speed command to a compatible variable-frequency drive. Each of its four outputs can use ±10 VDC voltage control, and the documented 15-bit resolution supports fine command granularity. Engineering must match output scaling to the drive's minimum and maximum reference inputs. Configure safe fault values, check common grounds, and test polarity at low command values before enabling full motor-start authority.

🧩

Current-Loop Process Transmitter Control

A ControlLogix installation can use the 1756-OF4's 0–20 mA outputs to drive compatible current-input field equipment when four loops must be controlled from one module. Current-loop wiring simplifies signal referencing, and the verified documentation lists open-circuit detection for current outputs. The module is non-isolated, so common-point effects must be evaluated. Confirm loop resistance, shield grounding, channel calibration, and disconnect behavior against the connected transmitter or controller datasheet.

⚙️

Positioning Axis Command Interface

The 1756-OF4 can translate ControlLogix position commands into analog velocity, speed, or position-reference signals for a compatible positioning controller. Voltage outputs provide bipolar command capability over ±10 VDC, while scaling maps controller engineering units to the axis interface. The four-channel arrangement can serve several axes or axes with redundant commands where system architecture permits. Calibrate each channel, define failsafe outputs, and verify that motion limits remain independent of analog-command scaling.

🔧

Industrial Test and Calibration Systems

The 1756-OF4 is useful in automated test fixtures that need programmable bipolar voltage or current injection into an instrument under test. Four channels allow sequential or parallel stimulus generation where the test architecture permits. Because the outputs are non-isolated, grounding relationships may prevent testing isolated devices simultaneously. Establish safe voltage and current limits, configure output ramps and clamp values, verify polarity, and include interlock hardware before the module drives external test equipment.

🏭

Machine Tool and Packaging Line Control

Machine-tool and packaging systems can use the 1756-OF4 to command proportional axes, pressure valves, or other analog actuators under ControlLogix supervision. Its 0°C to 60°C operating range and four output channels suit compact industrial I/O cabinets when ventilation and enclosure temperature are controlled. Series matters because Series B and C hardware consumes more power than Series A. Commissioning should include channel identification, full-scale checks, fault-state simulation, grounding verification, and controlled emergency-stop validation.

Zusammenfassung der empfohlenen Produkte

1756-OF4K ControlLogix four-channel analog current/voltage module family product with Add On Profile support Verwendet in: Proportional Control Valve Positioning, Variable-Speed Drive Speed Reference, Current-Loop Process Transmitter Control, Positioning Axis Command Interface, Industrial Test and Calibration Systems, Machine Tool and Packaging Line Control
What is the Allen-Bradley 1756-OF4?
The Allen-Bradley 1756-OF4 is a four-channel, non-isolated ControlLogix analog output module for voltage or current control. According to the Rockwell Automation product listing, it provides four outputs, ±10 VDC voltage operation, 0–20 mA current operation, a 20-pin removable terminal block, and an open-style enclosure for installation in a compatible ControlLogix chassis.
Where can I download the 1756-OF4 datasheet and pinout?
The official 1756-OF4 documentation is available from Rockwell Automation's product page at https://www.rockwellautomation.com/en-us/products/details.1756-OF4.html. The published PDF identifies a 20-pin module and provides field-connection information. Its field terminal is a removable terminal block rather than a conventional numbered IC package, so a complete public IC-style pinout was not supplied in the verified data.
What output ranges does the 1756-OF4 support?
The 1756-OF4 supports four configurable outputs operating as ±10 VDC voltage signals or 0–20 mA current signals. The verified Rockwell and distributor listings identify both ranges, while a service-manual source specifies current resolution of 650 nA per bit across 21 mA and voltage resolution of 320 µV per bit across 10.5 V.
Where can I buy the 1756-OF4 online?
The 1756-OF4 can be sourced through Rockwell Automation or authorized industrial distributors, including Radwell and Rexel, whose verified product links appear in the source data. Current unit pricing was not included in the supplied results, so XAIPART cannot publish a verified price as of 2026-10-21; request a quote for exact availability, condition, shipping, and authorized-channel confirmation.
What is the current price of the 1756-OF4?
A verified current price for the 1756-OF4 was not present in the supplied search results as of 2026-10-21. Octopart indicates that availability and pricing can be compared across two distributors, while Radwell lists an in-stock offering, but no numerical price was verified. Contact the seller for a current quotation rather than relying on an unverified historical figure.
What is the lead time for the 1756-OF4?
The verified 1756-OF4 lead time is typically 3–10 working days for in-stock items, subject to confirmation, according to Hde123. This commercial statement was retrieved on 2026-10-21 and does not guarantee every configuration or seller. Confirm current stock, shipping destination, manufacturer condition, and lead time before placing an order.
Is the 1756-OF4 in stock?
The supplied distributor evidence is mixed: Radwell describes the product as in stock, while the broader results do not provide a quantity or a universally current stock level. Availability can change rapidly for industrial automation modules. Confirm the quantity, Series A/B/C revision, warranty, and seller authorization before treating the module as available.
How long does the 1756-OF4 take to deliver?
A typical quoted delivery period is 3–10 working days for an in-stock 1756-OF4, subject to confirmation. This range comes from the verified Hde123 listing retrieved on 2026-10-21. It is not an XAIPART stock guarantee, so production shutdowns, obsolete inventory, module series, and expedited freight requirements should be confirmed before scheduling installation.
What can replace the 1756-OF4 as a drop-in module?
No verified drop-in replacement for the 1756-OF4 was identified in the supplied cross-reference data. A replacement must match the ControlLogix backplane, four-channel architecture, 20-pin terminal arrangement, ±10 VDC and 0–20 mA output capability, resolution, isolation, thermal conditions, and controller configuration. Functional substitutes that require wiring or configuration changes must not be treated as drop-in.
Can 1756-OF4K replace the 1756-OF4 module?
The 1756-OF4K cannot be confirmed as a drop-in replacement from the supplied evidence. Rockwell describes it as a ControlLogix four-point analog output current/voltage module with Add On Profiles for 1756-IF8, IF16, OF4, and OF8, but that software-profile compatibility does not establish physical, electrical, or functional interchangeability. Review the official product data before substitution.
Is there a cross-brand equivalent to the 1756-OF4?
No verified cross-brand drop-in equivalent to the 1756-OF4 was found. The verified replacement search produced Rockwell-family products, conversion systems, and generic cross-reference tools, but it did not identify another manufacturer's module with proven ControlLogix backplane, terminal, output-range, and programming compatibility. Cross-brand functional alternatives would require a separate engineering validation.
What is the difference between the 1756-OF4 and 1756-OF8?
The principal verified difference is channel count: the 1756-OF4 provides four analog outputs, while the 1756-OF8 is identified in the supplied search results as an eight-channel ControlLogix analog output module. They may serve related current/voltage-control applications, but the 1756-OF8 cannot be treated as a pin-for-pin four-channel drop-in replacement.
When should I choose the 1756-OF4 instead of a cross-brand analog module?
Choose the 1756-OF4 when the machine already uses a compatible Allen-Bradley ControlLogix system and needs four verified ±10 VDC or 0–20 mA non-isolated outputs on a 20-pin module. A cross-brand module should be considered only after verifying chassis backplane, electrical isolation, terminal mapping, output performance, environmental ratings, controller configuration, and long-term lifecycle support.
Is the 1756-OF4 suitable for control valves and variable-speed drives?
Yes, the 1756-OF4 is suitable for proportional control valves, variable-speed drives, and positioning systems. Its four selectable outputs can produce ±10 VDC commands for bipolar voltage-input equipment or 0–20 mA signals for compatible current-input devices. Configure scaling and fault states to keep actuators within safe limits during startup or controller failure.
How much backplane current does the 1756-OF4 consume?
The verified specification lists 150 mA at 5.1 VDC and 120 mA at 24 VDC from the ControlLogix backplane. These are different supply-condition values and should not be added together. Include the module, controller, communications adapters, and other installed modules when checking chassis and power-supply capacity.
What are the key specifications engineers should know about the 1756-OF4?
The key facts are four non-isolated analog outputs, ±10 VDC or 0–20 mA operation, 15-bit output resolution, a 20-pin removable terminal block, and a 0°C to 60°C operating range. The module also consumes 150 mA at 5.1 VDC or 120 mA at 24 VDC. Its open-circuit detection applies to current outputs.
Does the 1756-OF4 support open-circuit detection?
Yes, the 1756-OF4 provides open-circuit detection for current outputs. According to the verified service-manual summary, this feature helps identify a disconnected current-loop field device. It does not eliminate the need to verify polarity, loop resistance, shielding, grounding, and configured fault states during commissioning.

Technische Referenzdaten für 1756-OF4 – Vergleich, Designhinweise und Compliance-Informationen.

Auswahlhilfe

Choose the Allen-Bradley 1756-OF4 when maintaining or expanding a compatible ControlLogix installation that requires four non-isolated analog outputs. Its ±10 VDC voltage and 0–20 mA current modes support proportional valves, drives, positioning controllers, and process equipment, while scaling, ramping, clamping, programmable fault states, and current-loop open-circuit detection support commissioning and diagnostics. Verify the 20-pin terminal arrangement, module Series A/B/C revision, chassis power capacity, operating temperature, and controller configuration. No verified drop-in alternative was found, so an eight-channel 1756-OF8, a 1756-OF4K profile product, or a cross-brand analog module should not be assumed interchangeable. For new ControlLogix designs, obtain current Rockwell selection and compatibility information; for maintenance, prefer an authorized source and confirm module condition, warranty, and firmware compatibility.

Vergleich mit Alternativen

Parameter Dieses Produkt
Brand Allen-Bradley
Package Open-style ControlLogix module with 20-pin removable terminal block
Product Type Analog output module
Number of Analog Output Channels 4 channels
Voltage Output Range ±10 VDC
Current Output Range 0–20 mA
Output Resolution 15 bit
Output Isolation Non-isolated
Operating Temperature 0°C to 60°C
Backplane Current at 5.1 VDC 150 mA
Backplane Current at 24 VDC 120 mA
Current-Output Diagnostics Open-circuit detection

Designhinweise

Include the module in the chassis power-budget calculation using 150 mA at 5.1 VDC or 120 mA at 24 VDC, as applicable to the installed ControlLogix system. Rockwell states that Series B and C 1756-OF4 modules require more power than Series A modules. Check the exact module series, controller, chassis supply voltage, and all installed modules before maintenance; replacing an older revision with a newer high-power series can exceed an original supply design margin.

Install the 1756-OF4 only in a compatible ControlLogix chassis and use the correct 20-pin removable terminal block. Map each voltage or current channel individually and verify polarity before energizing outputs. Because the outputs are non-isolated, establish whether field devices share a common reference and avoid introducing unintended ground loops. Route command wiring away from high-energy motor and switching circuits where practical.

Do not treat 1756-OF4K software-profile support as proof of drop-in hardware equivalence. Similarly, an eight-channel 1756-OF8 or a generic cross-brand analog module is not a pin-compatible replacement merely because it supports voltage and current outputs. A safe replacement review must cover chassis backplane, terminal mapping, channel isolation, output range, resolution, fault behavior, environmental limits, controller configuration, and lifecycle support.

Compliance-Informationen

RoHS
Unknown
REACH
Unknown
AEC-Q100
Not Applicable
Bleifrei
Unknown
Halogenfrei
Unknown
Konfliktmineralien
Unknown

The supplied sources do not state RoHS, REACH, lead-free, halogen-free, or conflict-minerals status. The module is industrial programmable-controller hardware rather than an automotive electronic component.

Ähnliche Suchanfragen

Allen-Bradley 1756-OF4 1756-OF4 datasheet PDF 1756-OF4 specifications 1756-OF4 ±10 V 0-20 mA ControlLogix four-channel analog output module 1756-OF4 20-pin terminal block 1756-OF4 price buy 1756-OF4 online 1756-OF4 lead time 1756-OF4 drop-in replacement 1756-OF4 vs 1756-OF8 where to find 1756-OF4 pinout

Verwandte Bauteile & Begriffe

Allen-Bradley Rockwell Automation 1756-OF4 ControlLogix analog output module programmable logic controller industrial automation voltage output current output ±10 VDC 0–20 mA 15-bit resolution open-circuit detection non-isolated output 20-pin removable terminal block ControlLogix backplane proportional control valve variable-frequency drive 1756-TBSH 1756-OF4K 1756-OF8
Schnellangebot-RFQ
Geben Sie alle Details an – unser Vertriebsteam antwortet innerhalb von 24 Stunden
Teilenummer Hersteller Gehäuse QTY Zielpreis Gesamt
Gesamt: $0.00 USD
✓
Angebotsanfrage gesendet!

Wir antworten innerhalb von 24 Stunden auf Ihre E-Mail

1
RFQ gesendet
2
Angebot erhalten
3
Bestellung aufgegeben
4
Zahlung
5
Versandt
6
Geliefert
RFQ-Details ansehen