IO-LINK-MASTER02-USB - 1-Channel USB IO-Link Master | Pepperl+Fuchs
Артикул: IO-LINK-MASTER02-USB ✓ Активен| Кол-во | Цена за ед. | Итого |
|---|---|---|
| 1 | $220 | $220,00 |
| 10 | $199 | $1.990,00 |
| 25 | $185 | $4.625,00 |
| 50 | $172 | $8.600,00 |
| 100 | $159 | $15.900,00 |
IO-LINK-MASTER02-USB Обзор
An IO-Link master is the boundary device in an IO-Link communication system, sitting between the higher-level host (PLC, SCADA, or engineering PC) and the point-to-point IO-Link sensor. Within the hierarchy it belongs to: IO-Link master -> industrial communication gateway -> field-level network component -> industrial automation infrastructure. By exposing the IO-Link stack over USB, this master lets engineers configure and diagnose sensors without standing up a full PLC and PROFINET/EtherNet/IP infrastructure.
Key features include a 5-pin M12 A-coded sensor port per the IEC 61131-9 IO-Link standard, four front-panel status LEDs for power, USB link, IO-Link activity and fault, and an IP20 enclosure rated for cabinet and desktop use. The Mini-B USB 2.0 connector is forward-compatible with any standard USB-A to Mini-B cable shipped in the box, simplifying connection to a laptop. An optional 24 V DC auxiliary supply jack is provided for high-current 4-wire IO-Link devices that cannot be powered from the USB rail alone.
Typical applications include bench-level IO-Link sensor commissioning, firmware updates via FDT/DTM, factory-floor diagnostics on a maintenance laptop, training and demos for IO-Link technology, and pre-installation validation of sensor parameters before deployment on a production IO-Link master. It is widely used in industrial automation labs, sensor R&D, and field service toolkits.
When designing with this master, remember that the USB port provides limited current (typically 200 mA budget); sensors drawing more than that require the external 24 V supply. Always install the matching P+F FDT frame application before connecting sensors to ensure IODD interpreter files load correctly.
Аналоги без доработки для IO-LINK-MASTER02-USB — тот же корпус, pin-to-pin совместимость. Компоненты в других корпусах, требующие переработки PCB, исключены.
Инструмент быстрого сравнения — выберите альтернативные компоненты для сравнения бок о бок:
IO-LINK-MASTER01-USB
✅ Прямая замена ⚠️ Характеристики не проверены📋 Справочный аналог (нет в каталоге)
IOL-COM/USB
✅ Прямая замена📋 Справочный аналог (нет в каталоге)
IOLA2US-01101
✅ Прямая замена📋 Справочный аналог (нет в каталоге)
11048016
✅ Прямая замена📋 Справочный аналог (нет в каталоге)
USB IO-Link Configuration Tool
✅ Прямая замена📋 Справочный аналог (нет в каталоге)
TMG USB IO-Link Master V2 - EMC
✅ Прямая замена📋 Справочный аналог (нет в каталоге)
IO-LINK-MASTER02-USB Характеристики (опубликованы производителем)
| Product Type | IO-Link Master (USB to IO-Link gateway) |
| Number of IO-Link Channels | 1 (single-channel master) |
| Host Interface | USB 2.0 Mini-B plug-in connector |
| IO-Link Port Connector | M12 x 1, 5-pin socket, A-coded |
| Supported IO-Link Versions | V1.0 and V1.1 |
| Supply Voltage - USB (sensor power) | 5 V DC via USB |
| Supply Voltage - Auxiliary (jack) | 24 V DC (separate power supply, for high-current sensors) |
| Auxiliary Power Connector | 2.1 mm DC barrel jack |
| Status Indicators | 4 x LED (power, USB, IO-Link activity, fault) |
| Housing Material | Aluminum |
| Mass | approx. 100 g |
| Dimensions (W x H x D) | 41 mm x 24 mm x 54 mm |
| Degree of Protection | IP20 (when properly connected) |
| Тип монтажа | Desktop / portable |
| Configuration Software | Pepperl+Fuchs FDT/DTM tools (free download) |
| Функция | Process data exchange, parameterization, diagnostics for IO-Link devices |
Интерфейсы и разъемы IO-LINK-MASTER02-USB
IO-LINK-MASTER02-USB имеет следующие интерфейсы и разъемы, опубликованные производителем: USB, Входная мощность. Цоколевка разъемов расширения, нумерация контактов разъемов и электрические пределы определены в документации производителя.
| USB | 5 V DC via USB |
| Входная мощность | 24 V DC (separate power supply, for high-current sensors) |
Обратитесь к документации производителя для полной распиновки разъёма расширения и нумерации контактов соединителя.
Мощностные и тепловые характеристики
| Входная мощность | 5 V DC via USB |
Параметры входной мощности и тепловые параметры для IO-LINK-MASTER02-USB, опубликованные производителем.
Типичное применение
IO-LINK-MASTER02-USB подходит для 6 применениеs: IO-Link Sensor Commissioning on the Bench, Field Service and Maintenance Diagnostics, IO-Link Training and Demonstration, IO-Link Device Firmware Updates (FDT/DTM), Pre-Installation Sensor Validation, IO-Link Wireless Module Development (R&D).
IO-Link Sensor Commissioning on the Bench
The IO-LINK-MASTER02-USB is purpose-built for engineering-laptop commissioning of IO-Link V1.0/V1.1 sensors before they are deployed on a production IO-Link master. With its single 5-pin M12 A-coded port and USB 2.0 Mini-B host connection, engineers plug a sensor directly into the M12 socket, launch the free Pepperl+Fuchs FDT/DTM tools, and gain read/write access to all IODD-defined parameters, process data variables and diagnostic events. Compared to deploying a multi-port Ethernet IO-Link master + PLC stack for a single sensor bring-up, the IO-LINK-MASTER02-USB reduces setup time from hours to minutes and avoids allocating an IP address. The 4 status LEDs give instant visual feedback on power, USB link, IO-Link communication and fault state, which speeds up cable and wiring verification.
Рекомендуется
Field Service and Maintenance Diagnostics
Maintenance technicians carry the IO-LINK-MASTER02-USB as a portable diagnostic tool to interrogate suspect IO-Link sensors on the plant floor without disconnecting them from the network. Connected to a service laptop over USB and powered from the laptop's 5 V rail, it reads live process data, error codes and historical diagnostic logs from a single sensor via the M12 A-coded port. The auxiliary 24 V DC barrel-jack input allows powering 4-wire actuators when the USB 200 mA budget is insufficient. This makes the IO-LINK-MASTER02-USB a fast triage tool before swapping a sensor or escalating to a full PLC-based investigation, and the IP20 aluminum housing (100 g, 54x41x24 mm) fits a tool bag.
Рекомендуется
IO-Link Training and Demonstration
Training centers and sensor vendors use the IO-LINK-MASTER02-USB to teach IO-Link concepts because it isolates the IO-Link protocol from PLC, PROFINET and EtherNet/IP complexity. With one M12 A-coded port, one USB cable and free P+F FDT/DTM software, students see process data, IODD parameter structure and V1.1 data-storage behavior in real time on a single screen. The aluminum housing's compact 54 x 41 x 24 mm footprint and 100 g mass make it easy to ship between training rooms, and the 4 LEDs let instructors point to protocol state changes visually. The optional 24 V auxiliary jack lets the same unit demonstrate both USB-powered and externally-powered sensor topologies.
Рекомендуется
IO-Link Device Firmware Updates (FDT/DTM)
When a sensor vendor releases new firmware for an IO-Link device, the IO-LINK-MASTER02-USB provides a controlled environment to apply the update via the FDT/DTM workflow. Engineers connect the target sensor, launch the matching IODD interpreter in the P+F FDT frame, and the master carries the firmware image to the device over the C/Q line on Pin 4 of the M12 A-coded port. The auxiliary 24 V supply keeps the sensor powered during the update so the USB rail is not overloaded, and the 4 LEDs give a clear visual cue that IO-Link activity and any fault state are being managed. This avoids having to schedule a full PLC firmware-update window for one device.
Рекомендуется
Pre-Installation Sensor Validation
Before mounting a new IO-Link sensor on a machine, quality engineers validate it on the bench with the IO-LINK-MASTER02-USB to confirm parameter ranges, scaling behavior and diagnostic event generation. The 5-pin M12 A-coded IO-Link port and USB 2.0 Mini-B host interface let a laptop act as a virtual PLC, and the P+F FDT/DTM tools surface every IODD-defined parameter. The auxiliary 24 V DC input lets engineers simulate real-world supply conditions rather than the USB 5 V rail, which is critical for sensors whose accuracy depends on a stable 24 V supply. Identifying out-of-box failures at the bench reduces line-stop risk after installation.
Рекомендуется
IO-Link Wireless Module Development (R&D)
Sensor R&D teams use the IO-LINK-MASTER02-USB as a known-good USB-IO-Link reference while developing wireless IO-Link sensor prototypes. The master's M12 A-coded 5-pin port and standard IEC 61131-9 IO-Link electrical interface provide a reference C/Q waveform on Pin 4 that engineers can probe and compare against their wireless gateway implementation. With V1.0/V1.1 support, the P+F FDT/DTM stack exercises legacy and modern data-storage profiles that the prototype must also implement, and the 4 LEDs are useful for protocol-state bring-up debugging. The 100 g mass and Mini-B USB connector make it easy to embed on a lab bench next to oscilloscope probes.
Рекомендуется
Сводка рекомендуемых товаров
Справочные инженерные данные для IO-LINK-MASTER02-USB — сравнение, рекомендации по проектированию и информация о соответствии.
Руководство по выбору
Сравнение с аналогами
| Параметр | Этот товар | IO-LINK-MASTER01-USB | IOL-COM/USB | IOLA2US-01101 | 11048016 | USB IO-Link Configuration Tool |
|---|---|---|---|---|---|---|
| Brand | Pepperl+Fuchs | Pepperl+Fuchs | Turck | SICK | Baumer | Telco Sensors |
| Package / Form Factor | Aluminum desktop housing, 54 x 41 x 24 mm, 100 g | Same aluminum desktop form factor | Turck desktop housing, comparable footprint | SICK SiLink2 desktop housing | Baumer desktop housing | Telco desktop housing |
| Number of IO-Link Channels | 1 | 1 | 1 | 1 | 1 | 1 |
| IO-Link Port Connector | M12 x 1, 5-pin, A-coded | M12 x 1, 5-pin, A-coded | M12 A-coded 5-pin | M12 A-coded | M12 A-coded 5-pin | M12 5-pin plug |
| Host Interface | USB 2.0 Mini-B | USB 2.0 Mini-B | USB | USB | USB | USB 2.0 |
| IO-Link Version Support | V1.0 and V1.1 | V1.0 and V1.1 | V1.0 / V1.1 | V1.0 / V1.1 | V1.0 / V1.1 | V1.0 / V1.1 |
| Auxiliary Power Input | 24 V DC via 2.1 mm barrel jack | 24 V DC barrel jack | External supply option | External supply option | Multi-region PSU included (EU/KOR/USA/AUS/UK) | Optional power pack |
| Configuration Software | Pepperl+Fuchs FDT/DTM tools (free) | P+F FDT/DTM tools | Turck TBEN/DTM tools | SICK SOPAS | Baumer Sensor Suite | Telco configuration tool |
| Status LEDs | 4 (power, USB, IO-Link activity, fault) | 4 LEDs | Multiple LEDs | Multiple LEDs | Multiple LEDs | 4 status LEDs |
| Degree of Protection | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 |
Ключевые отличия
- Bundled vendor FDT/DTM stack with deep IODD library (против IOL-COM/USB (Turck))
- Auxiliary 24 V DC barrel jack for high-current sensors (против IOLA2US-01101 (SICK SiLink2))
- Four labeled status LEDs for fast protocol-state debugging (против USB IO-Link Configuration Tool (Telco))
- Compact 100 g aluminum housing for portable field service (против TMG USB IO-Link Master V2 - EMC)
Заметки по проектированию
The IO-LINK-MASTER02-USB can power a connected IO-Link sensor directly from the USB 5 V rail, but the USB 2.0 specification limits port current to 500 mA total and typical IO-Link sensor budgets on USB masters are 200 mA. For 4-wire IO-Link sensors or any device drawing more than 200 mA, connect a 24 V DC source to the 2.1 mm auxiliary barrel jack - per the P+F datasheet document 304074, the auxiliary input is the only way to deliver full IO-Link L+ current to the sensor's Pin 1.
Do not skip installing the Pepperl+Fuchs FDT frame application before plugging in the master. Without the FDT frame, the IODD interpreter files for individual sensors will not load and the user will see 'no IODD found' errors even when the sensor is electrically connected. Always connect the M12 A-coded cable, then launch the FDT frame, then attach the sensor-specific DTM package.
Although the IO-LINK-MASTER02-USB is a desktop device and not a PCB component, respect the M12 A-coded cable bend radius (typically > 10x cable diameter) and keep the Mini-B USB cable away from sources of EMI such as VFD motor cables - the IO-Link C/Q line on Pin 4 operates at 24 V pulse-modulated data rates up to 230.4 kbps (COM3) and can pick up noise on long parallel cable runs.
The IO-Link C/Q data line on Pin 4 of the M12 A-coded port is a half-duplex 24 V push-pull signal; cable capacitance degrades rise time. Per IEC 61131-9, standard IO-Link cable lengths are limited to 20 m. Do not substitute a generic 5-pin M12 sensor cable for an IO-Link-rated cable - non-IO-Link cables may not meet the 3 nF/m capacitance spec and can cause COM-port fallback to COM1 (4.8 kbps).
Информация о соответствии
Compliance statements (RoHS, REACH, lead-free, halogen-free, conflict minerals) were not present in the verified web data and are marked unknown. AEC-Q100 is not applicable for an industrial IO-Link master module. IP20 rating per IEC 60529 is confirmed from the manufacturer datasheet.