BMXNOR0200H 概述
An RTU (Remote Terminal Unit) communication module is a type of industrial communication interface that connects a Programmable Automation Controller (PAC) to SCADA master stations using telecontrol protocols. Within the automation hierarchy - RTU module, communication module, PAC platform, supervisory control and data acquisition system - it serves as the protocol gateway that bridges field-side RTU stations and the control platform, enabling telemetry exchange over Ethernet and serial links.
Key features include dual-protocol support for IEC 60870-5-101 (serial) and IEC 60870-5-104 (Ethernet), DNP3 telecontrol protocol support, a ruggedized 'H' build rated for severe environments, and native integration into the Modicon X80 module platform shared by the Modicon M580 and M340 PACs. According to Schneider Electric product documentation, the module operates from the rack's internal power supply with a current consumption of 95 mA at 24 V DC.
The BMXNOR0200H is an in-rack X80 module, which means it requires no separate enclosure, external power wiring, or standalone gateway commissioning. Configuration is performed through the same Unity Pro / EcoStruxure Control Expert software environment as the host M340 or M580 controller, reducing integration effort. The Modicon X80 shared-platform design also means one spare-part SKU and one training program cover both M580 and M340 installations.
Typical applications include water and wastewater telemetry, oil and gas pipeline SCADA, power generation and distribution substation automation, and other infrastructure remote monitoring where RTU master/slave protocol exchange with field RTU stations is required over serial or Ethernet links.
One design consideration: because this is the 'H' (harsh environment) variant, verify the extended environmental ratings against your installation profile before standardizing on the standard BMXNOR0200 for less severe cabinets.
This page synthesizes distributor availability, drop-in family alternatives, and practical deployment notes not found in the manufacturer datasheet.
直接替换替代料: BMXNOR0200H ——相同封装,引脚兼容。需要 PCB 改动的不同封装料号已排除。
快速对比工具——选择替代料号进行并排对比:
BMXNOR0200
✅ 直接替换 ⚠️ 规格未核验📋 参考替代料(不在目录中)
BMXNOR0200H 规格参数(制造商发布)
| Product Type | Ethernet / Serial RTU communication module |
| Platform Compatibility | Modicon X80 (Modicon M340, Modicon M580) |
| Ethernet Ports | 1 |
| Serial Ports | 1 |
| Connectors | 2 x RJ45 |
| Supported Protocols | IEC 60870-5-101, IEC 60870-5-104, DNP3 |
| Application | RTU protocol exchange with RTU stations (SCADA/telemetry) |
| Current Consumption | 95 mA at 24 V DC |
| Power Source | Internal power supply (rack-supplied) |
| Environmental Rating | Ruggedized for severe environments (H variant) |
| Mounting | Chassis mount (in-rack X80 module) |
| Configuration Software | EcoStruxure Control Expert / Unity Pro |
BMXNOR0200H 接口与连接器
BMXNOR0200H 提供制造商发布的以下接口和连接器:以太网。扩展排针引脚定义、连接器引脚编号和电气限值在制造商文档中定义。
| 以太网 | 1 |
请参阅 制造商文档 以查看完整的扩展排针引脚和连接器引脚编号。
功率与热特性
| 功耗 | 95 mA at 24 V DC |
BMXNOR0200H 的功率输入和热参数(由制造商发布)。
典型应用
BMXNOR0200H 适用于 6 应用s: Water and Wastewater SCADA Telemetry, Oil and Gas Pipeline Monitoring, Power Substation Automation, Infrastructure Remote Monitoring, Modicon M580 Control System Retrofit, Factory Floor SCADA Integration.
Water and Wastewater SCADA Telemetry
The BMXNOR0200H fits water and wastewater telemetry because IEC 60870-5-101/104 and DNP3 are the dominant telecontrol protocols between utility SCADA master stations and remote pump stations, reservoirs, and treatment plants. Its in-rack X80 form factor places the RTU gateway inside the existing Modicon M340 or M580 PAC chassis, so no separate gateway enclosure or extra 24 V DC wiring is needed - the module simply draws 95 mA at 24 V DC from the internal rack supply. Deployed via 2 x RJ45 ports (1 Ethernet, 1 serial), it can simultaneously serve an Ethernet IEC 104 or DNP3 master link and a legacy serial IEC 101 link to older field RTUs. The 'H' ruggedized build suits outdoor cabinets and humid well-site installations. Performance consideration: serial RTU polling rates are bounded by the IEC 101 link speed, so put high-priority points on the Ethernet 104 link for faster scan cycles.
推荐
Oil and Gas Pipeline Monitoring
Pipeline SCADA in oil and gas commonly standardizes on DNP3 and IEC 60870-5 telecontrol profiles, which the BMXNOR0200H supports natively, allowing a Modicon M580 PAC to act as the RTU-side device toward the master station while communicating with remote terminal units along the line. The module's severe-environment 'H' build addresses the temperature swings, dust, and humidity typical of pipeline block-valve stations and compressor sites. Because it is rack-mounted, engineering teams reuse the same X80 spares and EcoStruxure Control Expert project environment as the rest of the automation system, cutting training and maintenance cost. The 1 Ethernet + 1 serial port layout permits a primary DNP3 Ethernet link with a serial fallback. Plan the rack power budget around the module's 95 mA at 24 V DC consumption together with processor and I/O modules in the same chassis.
推荐
Power Substation Automation
In electrical substations, the BMXNOR0200H lets a Modicon M340 or M580 controller exchange IEC 60870-5-104 (Ethernet) and IEC 60870-5-101 (serial) data with the utility SCADA control center, and DNP3 where North American telecontrol conventions apply. The in-rack architecture avoids a standalone gateway cabinet: the module occupies an X80 rack slot beside the processor and I/O modules, powered from the rack internal supply at 95 mA at 24 V DC. The dual 2 x RJ45 connectivity supports a hardwired serial link to legacy protection or RTU equipment in parallel with the Ethernet master link - a common retrofit requirement in aging substations. Because the platform is shared between M580 and M340, utilities standardize one spare module across both PAC generations. Verify protocol profile settings (link address, common address, ASDU types) in EcoStruxure Control Expert to match the master station specification.
推荐
Infrastructure Remote Monitoring
Distributed infrastructure such as tunnels, highways, irrigation networks, and municipal assets often requires RTU-style polling over serial lines with gradual migration to Ethernet. The BMXNOR0200H addresses both phases in one module: 1 serial RJ45 port for legacy IEC 60870-5-101 field devices and 1 Ethernet RJ45 port for IEC 104 or DNP3 backhaul to the SCADA center. Its severe-environment rating suits roadside and outdoor cabinets with wide temperature and humidity exposure, and its X80 in-rack design means the telemetry function shares the same Modicon M340/M580 chassis as the local control logic, simplifying maintenance. Current consumption of 95 mA at 24 V DC keeps the module viable even in solar- or battery-backed cabinets where the rack power budget is tight. Configure redundant master links through the host PAC application logic for high-availability installations.
推荐
Modicon M580 Control System Retrofit
Facilities migrating from legacy RTU-based telemetry to the Modicon M580 PAC can retain their SCADA master configuration by using the BMXNOR0200H as the RTU protocol endpoint. Since the module belongs to the Modicon X80 platform, it installs in the same M580 rack as the processor and I/O modules and is configured inside the same EcoStruxure Control Expert project - no separate engineering tool is required. The module's IEC 60870-5-101/104 and DNP3 stack presents standard RTU data objects to the master station, so the SCADA side often needs only address remapping rather than a protocol rewrite. The 95 mA at 24 V DC internal-supply consumption and 2 x RJ45 connectivity keep wiring changes minimal during retrofit. Verify that the existing SCADA master's protocol profile (ASDU set or DNP3 object library) matches what the module exposes before commissioning.
推荐
Factory Floor SCADA Integration
Manufacturing plants that must report production and utility data (compressed air, water, power) to a corporate SCADA system over telecontrol protocols can embed the BMXNOR0200H in the plant's Modicon M340 or M580 PAC rack. Instead of deploying an additional protocol gateway in a control panel, the module uses the existing rack: it consumes 95 mA at 24 V DC from the internal supply and provides 2 x RJ45 ports for 1 Ethernet and 1 serial link. DNP3 and IEC 60870-5-104 support covers most energy-management and utility SCADA masters, while the serial port remains available for legacy metering or RTU equipment. The severe-environment 'H' build tolerates hot, dirty plant zones that exceed standard office-grade equipment ratings. A practical trade-off: protocol data throughput is shared with rack backplane traffic, so batch high-volume tags during off-peak polling windows.
推荐
推荐产品汇总
工程参考数据: BMXNOR0200H ——对比、设计指导和合规信息。
选型指南
与替代料对比
| 参数 | 本产品 | BMXNOR0200 |
|---|---|---|
| Package | X80 rack module (chassis mount) | X80 rack module (chassis mount) - same |
| Brand | Schneider Electric | Schneider Electric - same |
| Protocols | IEC 60870-5-101/104, DNP3 | IEC 60870-5-101/104, DNP3 |
| Ports | 1 Ethernet + 1 serial (2 x RJ45) | 1 Ethernet + 1 serial (2 x RJ45) |
| Environmental Grade | Severe environments (H variant) | Standard environments |
| Platform | Modicon X80 (M340 / M580) | Modicon X80 (M340 / M580) |
| Configuration Tool | EcoStruxure Control Expert / Unity Pro | EcoStruxure Control Expert / Unity Pro |
关键差异点
- Severe-environment qualification (对比 BMXNOR0200)
- In-rack X80 integration (对比 Standalone RTU gateways)
- Dual simultaneous protocol links (对比 BMXNOR0200 (single-link deployments))
设计说明
Budget the X80 rack power supply for the BMXNOR0200H at 95 mA at 24 V DC (about 2.28 W), drawn from the internal rack supply. Sum this with the processor module, all I/O modules, and any additional communication modules in the same chassis, then apply the usual 20-30% margin on the rack power supply rating. Because the module is rack-powered, no field-side power wiring or fused terminal is needed for the module itself - only the RJ45 communication cabling is field-terminated.
Do not treat the 'H' variant and the standard BMXNOR0200 as interchangeable in specifications reviews: the 'H' build is ruggedized for severe environments, and specifying the standard version for an outdoor or extreme-temperature cabinet is a common specification error. Also confirm that the SCADA master station's protocol profile (IEC 101 link address, IEC 104 ASDU set, or DNP3 object library) matches what the module exposes before FAT, since mismatches surface only during master-station integration testing.
Route the two RJ45 links with industrial Ethernet cabling practices: use shielded twisted pair (SFTP) rated for the cabinet environment, keep communication cabling separated from power conductors, and ground shields at one end per site EMC standard. On the serial link, observe line length limits for the chosen IEC 60870-5-101 baud rate - long serial runs over unshielded cable are the most frequent cause of intermittent telecontrol link failures. Consult Schneider Electric's X80 installation manuals for cabinet layout guidance.
For installations relying on the IEC 60870-5-101 serial link, verify grounding and isolation of the serial line, especially in substations where ground potential rise during faults can damage unisolated serial ports. Where long or electrically noisy serial runs are unavoidable, add external serial isolation/repeaters. On the Ethernet side, use managed switches supporting the required telecontrol latency; industrial-grade switches from vendors such as Moxa or Hirschmann are typical companions.