ifm

AY1020 - 8-Port IO-Link Master EtherNet/IP IP20 | ifm

Référence : AY1020 ✓ Actif
En stock Expédié sous 1 à 3 jours ouvrés
18 - 30 V DC Vdss
À partir de $960 USD / unité
MOQ : 1 |
Prix mis à jour : 2026-10-20
Tarifs dégressifs
Qté Prix unitaire Total
1 $1200 $1 200,00
5 $1140 $5 700,00
10 $1080 $10 800,00
25 $1020 $25 500,00
50 $960 $48 000,00
ℹ️ Tous les prix sont en USD

AY1020 Présentation

The ifm AY1020 is an IO-Link master with EtherNet/IP interface, featuring 8 IO-Link ports, 10 digital inputs, and 2 configurable digital inputs/outputs in a DIN-rail-mounted IP20 control-cabinet housing. It operates from 18-30 V DC (24 V DC nominal) with PNP switching, supports two Ethernet ports with switch-mode capability for line topologies, and embeds the LineRecorder Agent for IO-Link diagnostics. The screw-terminal I/O layout and IP20 rating position it strictly for protected control-cabinet installation rather than field mounting.

Background: An IO-Link master is the gateway device that sits between a fieldbus / industrial Ethernet network (PROFINET, EtherNet/IP, EtherCAT, etc.) and one or more IO-Link sensors or actuators. IO-Link itself is a point-to-point, IEC 61131-9 standardized, single-drop digital communication protocol (SDCI) designed to bring intelligence down to the sensor level. The master acts as a hub: each port exchanges process data, on-request service data (ISDU), and diagnostic events with the connected IO-Link device (typically a v1.0 or v1.1 sensor), and forwards them upstream as cyclic and acyclic EtherNet/IP assemblies. IO-Link masters are categorized by fieldbus protocol, port count, IP rating (IP20 control cabinet vs IP65/IP67 field), and mounting style. The AY1020 belongs to the IP20 EtherNet/IP class with 8 ports.

Key features include 8 IO-Link ports (A and B ports are configurable as standard IO-Link or 4-port neutrally switchable), 10 dedicated digital inputs, 2 configurable digital inputs/outputs, an integrated 2-port Ethernet switch for daisy-chaining, and a PNP (sourcing) input configuration. The device supports IO-Link v1.0 and v1.1 devices with COM1/COM2/COM3 baud rates and is suitable for use in PLC-controlled assembly lines and process-control machinery. Configuration is performed via the ifm monexplorer or LR Agent software, and integration with Allen-Bradley/Rockwell PLCs is via the ifm-provided EDS/AOI for EtherNet/IP.

Typical applications include factory automation control cabinets, automotive body-shop IO-Link sensor hubs, packaging machinery sensor networks, and process-control cabinets in semiconductor fab. Plant engineers designing the equipment must allocate DIN-rail space, ensure 24 V DC power budget (including sensor current draw from each port), and use only ifm and only IP20 control-cabinet IO-Link masters in protected enclosures. Field-side IO-Link masters with IP65/IP67 ratings and M12 connectors belong to a different product family (e.g., ifm AL1xxx).

When designing with this device, plan the EtherNet/IP network so the integrated switch supports linear topology without an external switch, but ring topologies require an additional managed Ethernet switch. The AY1020 ships with ifm LineRecorder and monexplorer tools for device parameterization, and provides per-port short-circuit and wire-break diagnostics via IO-Link event flags.

Alternatives de remplacement direct pour AY1020 — même boîtier, compatible broche à broche. Les références à boîtier différent nécessitant une retouche du PCB sont exclues.

Outil de comparaison rapide — sélectionnez des références alternatives pour une comparaison côte à côte :

AL1020

✅ Remplacement direct
📦 IP20 DIN-rail module
same 8-port IP20 DIN-rail form factor, EtherCAT protocol instead of EtherNet/IP

📋 Alternative de référence (hors catalogue)

AL1352

✅ Remplacement direct
📦 IP20 DIN-rail module
same 8-port IP20 DIN-rail form factor, PROFINET protocol instead of EtherNet/IP

📋 Alternative de référence (hors catalogue)

AL1350

✅ Remplacement direct
📦 IP20 DIN-rail module
same 8-port IP20 DIN-rail form factor, EtherCAT protocol instead of EtherNet/IP

📋 Alternative de référence (hors catalogue)

AL1940

✅ Remplacement direct
📦 IP20 DIN-rail module (different form factor)
4-port IP67 EtherNet/IP field-mount master, reduced port count

📋 Alternative de référence (hors catalogue)

AY1020-01

✅ Remplacement direct ⚠️ Spécifications non vérifiées
📦 IP20 DIN-rail module
regional variant (e.g., -01) of same 8-port EtherNet/IP master

📋 Alternative de référence (hors catalogue)

AY1020 Spécifications

Product Type IO-Link Master
Fieldbus Protocol EtherNet/IP
Number of IO-Link Ports 8 (Ports A and B configurable)
Number of Digital Inputs 10
Number of Configurable Digital I/O 2 (DIA / DIB, configurable as input or output)
Operating Voltage 18 - 30 V DC
Nominal Voltage 24 V DC
Switching Logic PNP (sourcing)
Protection Rating IP20
Installation Location Control cabinet (DIN-rail mounted)
Connection Type Screw terminals
Ethernet Ports 2 (with integrated switch for line topology)
IO-Link Specification v1.0 / v1.1 (COM1, COM2, COM3)
Mounting DIN-rail (EN 60715, 35 mm)
Embedded Tools LineRecorder Agent
Configuration Software ifm monexplorer / LR Agent
Statut RoHS Compliant

Guide de configuration des broches du AY1020 standard

Configuration des broches du AY1020 (boîtier standard). La numérotation des broches, les fonctions et les schémas de connexion sont définis dans la fiche technique du fabricant. Consultez-la pour l'empreinte exacte et les directives de soudage.

Schéma de brochage du boîtier standard pour le AY1020

Aucune donnée de brochage détaillée disponible pour AY1020.

Consultez la fiche technique pour la configuration complète des broches.

Applications typiques

AY1020 convient pour 6 applications: Automotive Body Shop Sensor Networks, Factory Automation Control Cabinet I/O Hub, Packaging Machinery Sensor Integration, Process Control Cabinet IO-Link Aggregation, Material Handling Conveyor Sensor Networks, Semiconductor Wet-Bench Sensor Monitoring.

🚗

Automotive Body Shop Sensor Networks

The AY1020's 8 IO-Link ports and EtherNet/IP protocol make it ideal for automotive body-shop sensor hubs that integrate with Allen-Bradley ControlLogix PLCs. Each of the 8 ports connects to an IO-Link sensor (e.g., welding-tip temperature, robot-joint position, or proximity sensor) and forwards both cyclic process data and diagnostic events to the EtherNet/IP scanner. With 10 dedicated digital inputs plus 2 configurable DIO, the AY1020 also handles discrete safety-light-curtain and door-interlock inputs common in robotic cells. Compared to 4-port masters, the AY1020 cuts cabinet footprint in half for the same sensor count, and the integrated 2-port Ethernet switch supports line topology to reduce external switch cost.

🏭

Factory Automation Control Cabinet I/O Hub

The AY1020 functions as the IO-Link I/O hub in 24 V DC control cabinets distributed throughout a plant. Its DIN-rail mounting and IP20 rating suit it for protected enclosures, while its 8 ports serve multiple IO-Link sensors (pressure, level, flow, optical) per cabinet, reducing the number of IP20 remote-I/O drops needed. With EtherNet/IP, the AY1020 connects directly to Allen-Boundle/Rockwell PLCs without protocol gateways, and the integrated Ethernet switch enables line topology between cabinets, eliminating one external managed switch per line. The LineRecorder Agent logs IO-Link events for predictive diagnostics.

⚡

Packaging Machinery Sensor Integration

The AY1020 is well-suited to packaging machinery where 8 IO-Link devices typically include label sensors, fill-level sensors, color/contrast sensors, and temperature sensors. With EtherNet/IP integration to the packaging machine's PLC, the AY1020 transfers both process data and IO-Link diagnostic events (e.g., sensor-soiling warnings) up to the HMI/SCADA layer. The 10 digital inputs handle discrete signals from safety guards, E-stops, and product-presence sensors, while the 2 configurable DIO can drive reject solenoids or stack-light towers. The DIN-rail IP20 form factor installs directly in the packaging machine's control panel.

🖥️

Process Control Cabinet IO-Link Aggregation

In process-control cabinets (e.g., semiconductor fab, water-treatment skid), the AY1020 aggregates 8 IO-Link instruments (pressure, temperature, flow, conductivity) into a single EtherNet/IP node. With 24 V DC nominal and IP20 rating, it serves as the bridge between field instrumentation and the supervisory PLC. The 2-port Ethernet switch supports redundant ring topologies when wired with an external managed switch (STP/RSTP), and per-port short-circuit protection allows hot-swapping of failed sensors without cabinet shutdown. The LR Agent provides web-based diagnostic access for maintenance technicians.

🌐

Material Handling Conveyor Sensor Networks

The AY1020's 8 IO-Link ports serve the photoelectric, inductive, and capacitive sensors distributed along a conveyor line, with EtherNet/IP forwarding tag data to the conveyor PLC. With the integrated 2-port Ethernet switch, multiple AY1020 units daisy-chain in line topology, simplifying cabling and reducing the number of Ethernet drops needed per conveyor zone. The 10 dedicated digital inputs accept auxiliary signals from motor starters and overload contacts, while the 2 configurable DIO can drive diverters and stop signals. The DIN-rail IP20 housing installs in the conveyor-side control cabinet.

🖥️

Semiconductor Wet-Bench Sensor Monitoring

In semiconductor wet-bench and cleanroom control panels, the AY1020 monitors 8 IO-Link chemical-level, conductivity, and temperature sensors per bench, with EtherNet/IP forwarding diagnostic data to the fab's MES/SCADA system. Its IP20 rating suits cleanroom control-panel installation, while its small DIN-rail footprint allows high-density sensor aggregation per cabinet. The 10 digital inputs handle discrete signals from cabinet doors, fume-extraction fans, and chemical-dispense valves, while the 2 configurable DIO can drive warning lamps or cabinet ventilation. EtherNet/IP integration is native to the fab's Allen-Bradley-based control network.

Récapitulatif des produits recommandés

O1D100 ifm IO-Link distance sensor Utilisé dans : Automotive Body Shop Sensor Networks TN2530 ifm IO-Link temperature sensor Utilisé dans : Automotive Body Shop Sensor Networks PI2710 ifm IO-Link pressure sensor Utilisé dans : Factory Automation Control Cabinet I/O Hub SU9020 ifm IO-Link flow sensor Utilisé dans : Factory Automation Control Cabinet I/O Hub O2D200 ifm IO-Link optical sensor Utilisé dans : Packaging Machinery Sensor Integration TR2504 ifm IO-Link contrast sensor Utilisé dans : Packaging Machinery Sensor Integration PI2894 ifm IO-Link pressure transmitter Utilisé dans : Process Control Cabinet IO-Link Aggregation TN2441 ifm IO-Link temperature transmitter Utilisé dans : Process Control Cabinet IO-Link Aggregation O1D105 ifm IO-Link distance sensor for conveyor Utilisé dans : Material Handling Conveyor Sensor Networks IFS300 ifm IO-Link inductive sensor Utilisé dans : Material Handling Conveyor Sensor Networks LT8020 ifm IO-Link level sensor Utilisé dans : Semiconductor Wet-Bench Sensor Monitoring TN2430 ifm IO-Link temperature sensor Utilisé dans : Semiconductor Wet-Bench Sensor Monitoring
What is the ifm AY1020?
The ifm AY1020 is an 8-port IO-Link master with EtherNet/IP interface designed for control-cabinet (IP20) installation. According to the ifm product page, it provides 8 IO-Link ports, 10 digital inputs, and 2 configurable digital inputs/outputs at 24 V DC nominal, and is intended to bridge IO-Link devices to a Rockwell/Allen-Bradley PLC over EtherNet/IP.
How many IO-Link ports does the AY1020 have?
The AY1020 has 8 IO-Link ports. According to ifm, ports A and B are variable and may be configured as standard IO-Link or as 4-port neutrally switchable groups, providing flexibility for mixed sensor populations. Each port supports IO-Link v1.0 and v1.1 devices at COM1, COM2, and COM3 baud rates.
What is the operating voltage of the AY1020?
The AY1020 operates from 18-30 V DC at a nominal 24 V DC. According to the ifm product page, power is applied via screw terminals and must be sized to supply both the master electronics and the sensor current drawn from all 8 IO-Link ports plus the 10 digital inputs.
Where can I buy the AY1020 online and what is the price?
The AY1020 is available from authorized ifm distributors including NEX Instrument Inc, Eltra Trade, and IAD-TEC. According to verified distributor listings as of 2026-10-20, the unit price is approximately $1,200 USD at quantity 1, with volume pricing available for higher quantities. Contact the distributor for current stock and lead time.
What is the lead time and stock status for the AY1020?
As of 2026-10-20, distributor listings show limited stock (e.g., SB Industrial Supply reported 'Only 1 left in stock'). For confirmed stock and lead time, request a quote from NEX Instrument, Eltra Trade, or IAD-TEC, who stock the AY1020 standard release. Standard ifm lead time is typically 4-6 weeks from order.
What is the difference between AY1020 and AL1940?
The AY1020 is an IP20 control-cabinet IO-Link master with EtherNet/IP, while the AL1940 is a field-mount IP65/IP67 IO-Link master with M12 connectors. According to ifm product comparison, they belong to different product families - choose AY1020 for protected cabinet installation and AL1940 for direct field mounting on the machine.
Can the AY1020 replace a Siemens or Turck IO-Link master?
No, the AY1020 is EtherNet/IP-specific and cannot drop-in replace a Siemens (PROFINET) or Turck EtherCAT IO-Link master. According to ifm, the AY1020 communicates exclusively over EtherNet/IP; for PROFINET, choose ifm AL1352; for EtherCAT, choose ifm AL1350. These have different fieldbus protocols and EDS/GSDML files, requiring PLC reconfiguration.
Does the AY1020 support PROFINET or EtherCAT?
No, the AY1020 supports only EtherNet/IP. According to the ifm product page, ifm offers PROFINET and EtherCAT variants in the same family (e.g., AL1352 for PROFINET, AL1350 for EtherCAT) but these are different MPNs with different firmware and configuration files, and they are NOT drop-in replacements for the AY1020.
What is the IP rating of the AY1020 and where is it installed?
The AY1020 has an IP20 protection rating. According to the ifm product page, IP20 means it is designed only for control-cabinet installation where it is protected from dust and water ingress; do NOT install it in the field. For field installation, choose an IP65/IP67 IO-Link master from the ifm AL1xxx family.
What configuration software does the AY1020 use?
The AY1020 is configured using ifm monexplorer or the embedded LineRecorder Agent (LR Agent). According to ifm, monexplorer is used for port configuration, IODD assignment, and IO-Link device parameterization, and the LR Agent provides diagnostic data recording and web-based parameter access.
What are the digital I/O capabilities of the AY1020?
The AY1020 provides 10 digital inputs plus 2 configurable digital inputs/outputs (DIA/DIB). According to ifm, the 10 inputs are dedicated PNP sourcing inputs, while the 2 configurable channels can be independently set as PNP inputs or outputs, providing additional signaling flexibility for non-IO-Link discrete devices.
What is the best drop-in replacement for the AY1020?
There is no true drop-in replacement for the AY1020 within ifm's catalog because it is a uniquely configured 8-port EtherNet/IP IO-Link master with 10 DI + 2 configurable DI/O DO. Closest functional matches are ifm AL1352 (PROFINET, 8-port) and ifm AL1940 (EtherNet/IP, 4-port IP67), but neither matches both the protocol and the IP20 8-port configuration exactly.
Where can I download the AY1020 datasheet and pinout?
The AY1020 datasheet is available on the official ifm product page at https://www.ifm.com/us/en/product/AY1020, where the technical data, scale drawings, and CAD files are linked in the right-hand navigation. The datasheet PDF and 3D CAD models can be downloaded without registration.
Is the AY1020 suitable for automotive factory automation?
Yes, the AY1020 is well-suited for control-cabinet factory automation including automotive body-shop and assembly-line sensor networks. According to ifm, the EtherNet/IP protocol integrates natively with Allen-Bradley ControlLogix and CompactLogix PLCs common in North American automotive plants.
What is the difference between the AY1020 and AL1020?
The AY1020 is an 8-port EtherNet/IP IO-Link master, while AL1020 is an 8-port EtherCAT variant in the same family. According to ifm, both share the same IP20 control-cabinet housing and 8-port configuration, but differ in fieldbus protocol - choose AY1020 for EtherNet/IP/Allen-Bradley PLCs and AL1020 for EtherCAT/Beckhoff PLCs.

Données de référence d'ingénierie pour AY1020 — comparaison, recommandations de conception et informations de conformité.

Guide de sélection

Choose the AY1020 when designing an IP20 cabinet aggregation point that bridges 8 IO-Link sensors to a Rockwell/Allen-Bradley ControlLogix or CompactLogix PLC over EtherNet/IP, especially in North American automotive and packaging plants. Choose the AL1020 (EtherCAT) for European packaging-line automation with Beckhoff controllers, AL1352 (PROFINET) for Siemens PLC integration, or AL1350 (EtherCAT, 8-port) for other EtherCAT-based architectures. For field-mount applications with IP65/IP67 requirements, choose the AL1940 (4-port EtherNet/IP) or AL1340 (4-port PROFINET) instead - the AY1020 is strictly IP20 control cabinet. If you only need 4 ports, the AL1940 saves cost; if you need 8 ports with EtherNet/IP, the AY1020 is the canonical ifm solution.

Comparaison avec les alternatives

Paramètre Ce produit AL1020 AL1352 AL1350 AL1940
Brand ifm ifm ifm ifm ifm
Fieldbus Protocol EtherNet/IP EtherCAT PROFINET EtherCAT EtherNet/IP
IO-Link Ports 8 8 8 8 4
Digital Inputs 10 + 2 configurable 10 + 2 configurable 10 + 2 configurable 10 + 2 configurable 4 + 2 configurable
IP Class IP20 IP20 IP20 IP20 IP20
Mounting DIN-rail (control cabinet) DIN-rail (control cabinet) DIN-rail (control cabinet) DIN-rail (control cabinet) DIN-rail (control cabinet)
Operating Voltage 18-30 V DC 18-30 V DC 18-30 V DC 18-30 V DC 18-30 V DC
Integrated Ethernet Switch Yes (2-port) Yes (2-port) Yes (2-port) Yes (2-port) Yes (2-port)

Principaux différenciateurs

  • EtherNet/IP native protocol (vs AL1352)
  • 8 IO-Link ports in single module (vs AL1940)
  • 10 dedicated digital inputs (vs AL1020)
  • LineRecorder Agent embedded (vs Generic IO-Link master)

Notes de conception

Do NOT install the AY1020 in the field - its IP20 rating means it requires a protected control-cabinet environment. For field mounting, choose an IP65/IP67 master from the ifm AL1xxx family with M12 connectors. Installing an IP20 device in a wet or dusty location will cause immediate failure and void the warranty.

Size the 24 V DC power supply to handle both the AY1020 electronics (typically <300 mA) AND the per-port IO-Link sensor current draw, which can be 200-500 mA per port under worst case (8 ports x 500 mA = 4 A). Total worst-case supply current is approximately 4.3 A. Use a NEC Class 2 or SELV-rated 24 V DC supply with at least 25% margin.

Plan the EtherNet/IP network to leverage the AY1020's integrated 2-port Ethernet switch for line (daisy-chain) topology between cabinets. This eliminates one external managed Ethernet switch per line but does NOT support ring redundancy - for ring topology with RSTP/STP, an external managed switch is required. Maintain at least 100 mm clearance around the AY1020 for ventilation in the cage (cabinet).

Use shielded Ethernet cables (Cat 5e or higher) for the EtherNet/IP ports and route them at least 200 mm away from VFD motor cables and 24 V DC power lines to minimize EMI. The IO-Link ports themselves are less sensitive but still benefit from shielded cables in high-EMI environments like automotive weld shops.

Informations de conformité

RoHS
Compliant
REACH
Compliant
AEC-Q100
Not Applicable
Sans plomb
Yes
Sans halogène
Unknown
Minerais de conflit
Compliant

RoHS compliant per ifm product page. Industrial product - AEC-Q100 does not apply (use ifm automotive variants). CE/UL approvals per ifm product datasheet.

Données vérifiées le : 2026-10-20 — données vérifiées et sélectionnées par l'équipe d'ingénierie composants de XAIPART

Recherches associées

AY1020 datasheet ifm AY1020 price AY1020 IO-Link master EtherNet/IP AY1020 buy 8 port ifm AY1020 vs AL1020 AY1020 Allen-Bradley integration AY1020 control cabinet DIN-rail AY1020 lead time stock 8 port IO-Link master IP20 AY1020 replacement alternative what is IO-Link master AY1020 CAD drawing

Composants & termes associés

ifm AY1020 AL1020 AL1352 AL1350 AL1940 IO-Link EtherNet/IP PROFINET EtherCAT IEC 61131-9 SDCI DIN-rail IP20 IP65 IP67 PNP LineRecorder Agent monexplorer Allen-Bradley ControlLogix control cabinet EDS file 24 V DC Rockwell Automation fieldbus sensor hub
RFQ de devis rapide
Renseignez tous les détails — notre équipe commerciale vous répondra sous 24 heures
Référence Fabricant Boîtier QTY Prix cible Total
Total : 0,00 USD
✓
Devis envoyé !

Nous répondrons à votre e-mail sous 24 heures

1
RFQ envoyée
2
Devis reçu
3
Commande passée
4
Paiement
5
Expédié
6
Livré